Specification of FP3710-T42-U
Model (Global Code): FP3710-T42-U (PFXFP3710T2AU)
Functional Specification
Display Type |
TFT Color LCD |
Display Size |
15" |
Resolution |
1,024 x 768 pixels (XGA) |
Dot pitch |
W0.297 x H0.297 mm [W0.01 x H0.01 in.] |
Effective Display Area |
W304.1 x H228.1 mm [W11.97 x H8.98 in.] |
Display Colors |
16,777,216 Colors |
Backlight |
CCFL (Replaceable) |
Brightness Control |
Available*1 |
Contrast Control |
Available |
Backlight Service Life |
50,000 hrs. or more (continuous operation at 25 °C before backlight brightness decreases to 50% or backlight starts to blink) |
Touch Panel Type |
Resistive Film (analog) |
Touch Panel Resolution |
1,024 x 1,024 |
Touch Panel Service Life |
1,000,000 times or more |
Touch Panel Interface |
RS-232C or USB (USB2.0, TYPE-B) |
Interface |
USB (TYPE-A) |
Conforms to USB2.0 (TYPE-A) x 1, Power Supply Voltage: DC 5 V ±5 %, Output Current: 500 mA or less, Communication Distance: 5 m or less |
Video |
Analog RGB input connector: mini D-Sub15 (socket) x 1,
DVI-D input, Connector: DVI-D 24 pin (socket) x 1*2 |
-
*1 Specified on OSD setting.
-
*2 FPs which have a mark in hardware revision "2" support DVI Hot Plug Detect function.
General Specification
International Safety Standards |
|
Rated Input Voltage |
AC 100 to 240 V |
Input Voltage Limits |
AC 85 to 264 V |
Rated frequency |
50/60 Hz |
Rated frequency range |
40 to 72 Hz |
Allowable Voltage Drop |
1 cycle or less(Voltage drop interval must be 1 second or more.) |
Power Consumption |
AC 100 V: 110 VA or less, AC 240 V: 168 VA or less |
In-Rush Current |
60 A or less |
Voltage Endurance |
AC 1,500 V 20 mA for 1 min (between charging and FG terminals) |
Insulation Resistance |
DC 500 V, 10 MΩ or more (between charging and FG terminals) |
Surrounding Air Temperature |
0 to 50 °C |
Storage Temperature |
-20 to +60 °C |
Ambient Humidity |
10 to 90 % RH (Wet bulb temperature: 39 °C or less - no condensation.) |
Storage Humidity |
10 to 90 % RH (Wet bulb temperature: 39 °C or less - no condensation.) |
Dust |
0.1 mg/m³ or less (non-conductive levels) |
Pollution Degree |
For use in Pollution Degree 2 environment |
Atmosphere |
Free of corrosive gases |
Air Pressure (altitude range) |
800 to 1,114 hPa (2,000 m above sea level or less) |
Vibration Resistance |
IEC/EN61131-2 compliant, 5 to 9 Hz Single amplitude 3.5 mm [0.14 in.], 9 to 150 Hz Fixed acceleration: 9.8 m/s², X, Y, Z directions for 10 cycles (100 min) |
Concussion Resistance |
IEC/EN61131-2 compliant, 147 m/s², X, Y, Z directions for 3 times |
Noise Immunity |
Noise Voltage: 1,500 Vp-p, Pulse Duration: 1 µs, Rise Time: 1 ns, (via noise simulator) |
Electrostatic Discharge Immunity |
Contact Discharge Method: 6 kV (IEC/EN61000-4-2 Level 3) |
Grounding |
Protective grounding: Grounding resistance of 100 Ω, 2 mm² or thicker wire, or your country's applicable standard. (Same for FG and SG terminals) |
Structure |
Equivalent to IP65f (on the front panel when properly installed in an enclosure)*3 |
Installation Configuration |
Embedded panel |
Cooling Method |
Natural air circulation |
Weight Approx. |
7 kg [15.4 lb] or less (display unit only) |
External Dimensions |
W395 x H294 x D60 mm [W15.55 x H11.57 x D2.36 in.] |
Panel Cut Dimensions |
W383.5 x H282.5 mm [W15.1 x H11.12 in.], Panel thickness area: 1.6 to 10 mm [0.06 to 0.39 in.]*4 |
-
*3 The front face of the FP unit, installed in a solid panel, has been tested using conditions equivalent to the standards shown in the specification. Even though the FP unit's level of resistance is equivalent to these standards, oils that should have no effect on the FP can possibly harm the unit. This can occur in areas where either vaporized oils are present, or where low viscosity cutting oils are allowed to adhere to the unit for long periods of time. If the FP's front face protection sheet becomes peeled off, these conditions can lead to the ingress of oil into the FP and separate protection measures are suggested., Also, if non-approved oils are present, it may cause deformation or corrosion of the front panel's plastic cover. Therefore, prior to installing the FP be sure to confirm the type of conditions that will be present in the FP's operating environment., If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from the panel, the original level of the protection cannot be guaranteed. To maintain the original protection level, be sure to replace the installation gasket regularly.
-
*4 Regarding dimensional tolerance, everything +1/-0 mm [+0.04/-0 in.] and R in angle are below R3 [R0.12 in.].
External Dimensions / Interfaces / Panel Cut-out
|