DOWNLOADS

 

 

OVERVIEW

 

Features

  • Pressure measuring range: 100 mbar … 1000 bar
  • Accuracy: ≤ ± 0.10 / 0.05 % FS
  • Operating temperature: -40 … 125°C
  • Process temperature: -40 … 150°C
  • Output signal: 0 … 5 / 0 … 10 VDC, 4 … 20 mA
  • Total Error Band: ≤ ± 0.30 %FS (0 … 70°C)
  • Materials: Stainless steel, Titanium
  •  

Customer benefits

 

  • Pressure measuring range: 100 mbar … 1000 bar
  • Accuracy: ≤ ± 0.10 / 0.05 % FS
  • Operating temperature: -40 … 125°C
  • Process temperature: -40 … 150°C
  • Output signal: 0 … 5 / 0 … 10 VDC, 4 … 20 mA
  • Total Error Band: ≤ ± 0.30 %FS (0 … 70°C)
  • Materials: Stainless steel, Titanium
Back to Top

SPECIFICATIONS

Pressure measuring range (bar)

  0.1 ... 0.5 (1) > 0.5 ... 2 > 2 ... 100
Overpressure 3 bar 3 x FS (≥ 3 bar) 3 x FS
Burst pressure, (5) > 200 bar > 200 bar > 850 bar
Accuracy, (6), (± % FS) ≤ 0.10 ≤ 0.10 / ≤0.05 (9) ≤ 0.10 / ≤0.05 (9)
Total Error, (7), 
(± % FS ; typ. / max.)
     
-25...100 °C compensated / Allowed process temperature -40...150°C, (8) ≤ 1.3 / 1.5 ≤ 0.75 / 1.0 ≤ 0.75 / 1.0
-25...100 °C compensated / Allowed process temperature -40...150°C, (9) n.a. ≤ 0.3 / 0.6 ≤ 0.3 / 0.6
-40...125 °C compensated / Allowed process temperature -40...150°C, (9) n.a. ≤ 0.5 / 0.8 ≤ 0.5 / 0.8
-40...100°C compensated / Allowed process temperature -40...150°C, (8) ≤ 1.5 / 2.0 ≤ 1.0 / 1.5 ≤ 1.0 / 1.25
0...70 °C compensated / Allowed process temperature -40...150°C, (8) ≤ 0.5 / 1.0 ≤ 0.2 / 0.4 ≤ 0.1 / 0.3
0...70 °C compensated / Allowed process temperature -40...150°C, (9) n.a. ≤ 0.1 / 0.2 ≤ 0.1 / 0.2
Response time, (typ.) < 1ms / 10...90% FS < 1ms / 10...90% FS < 1ms / 10...90% FS
Long term stability, (10) < 0.5% FS / < 4 mbar < 0.2% FS / < 4 mbar < 0.1% FS / < 0.2% FS
  > 100 ... 600, (2), (4) > 600 ... 1000, (3)
Overpressure 3 x FS (≤ 850 / ≤ 1500 bar) 1500 bar
Burst pressure, (5) > 850 / ≤ 1500 bar > 1500 bar
Accuracy, (6), (± % FS) ≤ 0.10 ≤ 0.25
Total Error, (7), 
(± % FS ; typ. / max.)
   
-25...100 °C compensated / Allowed process temperature -40...150°C, (8) ≤ 0.75 / 1.0 ≤ 0.75 / 1.0
-25...100 °C compensated / Allowed process temperature -40...150°C, (9) n.a. n.a.
-40...125 °C compensated / Allowed process temperature -40...150°C, (9) n.a. n.a.
-40...100°C compensated / Allowed process temperature -40...150°C, (8) ≤ 1.0 / 1.25 ≤ 1.0 / 1.25
0...70 °C compensated / Allowed process temperature -40...150°C, (8) ≤ 0.3 / 0.5 ≤ 0.3 / 0.5
0...70 °C compensated / Allowed process temperature -40...150°C, (9) n.a. n.a.
Response time, (typ.) < 1ms / 10...90% FS < 1ms / 10...90% FS
Long term stability, (10) < 0.1% FS / < 0.2% FS < 0.1% FS / < 0.2% FS

Temperature range

   
Operating temperature -40...125 °C
Process temperatur -40...150 °C
Storage temperatur -40...125 °C

Electrical specifications

  4 ... 20 mA 0 ... 5 V 0 ... 10 V
Power supply 9…33 V DC 10...30 V DC 12...30 V DC
Supply influence < 0.05% FS < 0.05% FS < 0.05% FS
Current consumption      
Circuit diagram
Load resistance
Load influence < 0.05% FS < 0.05% FS < 0.05% FS

Physical specifications

Back to Top

CERTIFICATES

 

 CE Declaration of Cinfirmity 2016-04-13

 RoHS

 
 

 


Please register here in order to access the download page.
Name: *
Email address: *
Company Name: *
Designation: *
Contact No: *
 
  * Please filled in the required details.