Key specifications
200 V drive ratings (200 V to 240 V ±10%)
MODEL
|
NORMAL DUTY
|
HEAVY DUTY
|
|
MAXIMUM
CONT.
OUTPUT CURRENT
|
NOMINAL
POWER
AT 220V
|
MOTOR
POWER
AT 230V
|
PEAK CURRENT
|
MAXIMUM
CONT.
OUTPUT CURRENT
|
OPEN LOOP PEAK CURRENT
|
CLOSED LOOP PEAK CURRENT
|
NOMINAL
POWER
AT 220V
|
MOTOR
POWER
AT 230V
|
|
|
|
A
|
kW
|
hp
|
A
|
A
|
A
|
A
|
kW
|
hp
|
|
|
0201
|
|
|
|
|
2.2
|
3.3
|
3.8 (3.3)*
|
0.37
|
0.5
|
|
0202
|
|
|
|
|
3.1
|
4.6
|
5.4 (4.6)*
|
0.55
|
0.75
|
|
0203
|
|
|
|
|
4.0
|
6.0
|
7.0 (6.0)*
|
0.75
|
1.0
|
|
0204
|
|
|
|
|
5.7
|
8.5
|
9.9 (8.5)*
|
1.1
|
1.5
|
|
0205
|
|
|
|
|
7.5
|
11.2
|
13.1 (11.2)*
|
1.5
|
2.0
|
|
|
1201
|
5.2
|
1.1
|
1.5
|
5.7
|
4.3
|
6.4
|
7.5
|
0.75
|
1.0
|
|
1202
|
6.8
|
1.5
|
2.0
|
7.4
|
5.8
|
8.7
|
10.1
|
1.1
|
1.5
|
|
1203
|
9.6
|
2.2
|
3.0
|
10.5
|
7.5
|
11.2
|
13.1
|
1.5
|
2.0
|
|
1204
|
11
|
3.0
|
3.0
|
12.1
|
10.6
|
15.9
|
18.5
|
2.2
|
3.0
|
|
|
2201
|
15.5
|
4.0
|
5.0
|
17.0
|
12.6
|
18.9
|
22
|
3.0
|
3.0
|
|
2202
|
22
|
5.5
|
7.5
|
24.2
|
17
|
25.5
|
29.7
|
4.0
|
5.0
|
|
2203
|
28
|
7.5
|
10
|
30.8
|
25
|
37.5
|
43.7
|
5.5
|
7.5
|
|
|
3201
|
42
|
11
|
15
|
46
|
31
|
46.5
|
54.2
|
7.5
|
10
|
|
3202
|
54
|
15
|
20
|
59
|
42
|
63
|
73.5
|
11
|
15
|
|
|
4201
|
68
|
18.5
|
25
|
74
|
56
|
84
|
98
|
15
|
20
|
|
4202
|
80
|
22
|
30
|
88
|
68
|
102
|
119
|
18.5
|
25
|
|
4203
|
104
|
30
|
40
|
114
|
80
|
120
|
140
|
22
|
30
|
|
|
5201
|
130
|
37
|
50
|
143
|
105
|
157
|
183
|
30
|
40
|
|
5202
|
154
|
45
|
60
|
169
|
130
|
195
|
227
|
37
|
50
|
|
400 V drive ratings (380 V to 480 V ±10%
MODEL
|
NORMAL DUTY
|
HEAVY DUTY
|
|
MAXIMUM
CONT.
OUTPUT CURRENT
|
NOMINAL
POWER
AT 400V
|
MOTOR
POWER
AT 460V
|
PEAK CURRENT
|
MAXIMUM
CONT.
OUTPUT
CURRENT
|
OPEN LOOP PEAK CURRENT
|
CLOSED LOOP PEAK CURRENT
|
NOMINAL
POWER
AT 400V
|
MOTOR
POWER
AT 460V
|
|
|
|
A
|
kW
|
hp
|
A
|
A
|
A
|
A
|
kW
|
hp
|
|
|
0401
|
|
|
|
|
1.3
|
1.9
|
2.2
|
0.37
|
0.5
|
|
0402
|
|
|
|
|
1.7
|
2.5
|
2.9
|
0.55
|
0.75
|
|
0403
|
|
|
|
|
2.1
|
3.1
|
3.6
|
0.75
|
1.0
|
|
0404
|
|
|
|
|
3.0
|
4.5
|
5.2
|
1.1
|
1.5
|
|
0405
|
|
|
|
|
4.2
|
6.3
|
7.3
|
1.5
|
2.0
|
|
|
1401
|
2.8
|
1.1
|
1.5
|
3.0
|
2.1
|
3.1
|
3.6
|
0.75
|
1.0
|
|
1402
|
3.8
|
1.5
|
2.0
|
4.1
|
3.0
|
4.5
|
5.2
|
1.1
|
1.5
|
|
1403
|
5.0
|
2.2
|
3.0
|
5.5
|
4.2
|
6.3
|
7.3
|
1.5
|
2.0
|
|
1404
|
6.9
|
3.0
|
5.0
|
7.5
|
5.8
|
8.7
|
10.1
|
2.2
|
3.0
|
|
1405
|
8.8
|
4.0
|
5.0
|
9.6
|
7.6
|
11.4
|
13.3
|
3.0
|
5.0
|
|
1406
|
11
|
5.5
|
7.5
|
12.1
|
9.5
|
14.2
|
16.6
|
4.0
|
5.0
|
|
|
2401
|
15.3
|
7.5
|
10
|
16.8
|
13
|
19.5
|
22.7
|
5.5
|
10
|
|
2402
|
21
|
11
|
15
|
23
|
16.5
|
24.7
|
28.8
|
7.5
|
10
|
|
2403
|
29
|
15
|
20
|
31
|
25
|
34.5
|
40.2
|
11
|
20
|
|
2404
|
|
|
|
|
29
|
43.5
|
50.7
|
15
|
20
|
|
|
3401
|
35
|
18.5
|
25
|
38
|
32
|
48
|
56
|
15
|
25
|
|
3402
|
43
|
22
|
30
|
47
|
40
|
60
|
70
|
18.5
|
30
|
|
3403
|
56
|
30
|
40
|
61
|
46
|
69
|
80.5
|
22
|
30
|
|
|
4401
|
68
|
37
|
50
|
74
|
60
|
90
|
105
|
30
|
50
|
|
4402
|
83
|
45
|
60
|
91
|
74
|
111
|
129.5
|
37
|
60
|
|
4403
|
104
|
55
|
75
|
114
|
96
|
144
|
168
|
45
|
75
|
|
|
5401
|
138
|
75
|
100
|
151
|
124
|
186
|
217
|
55
|
100
|
|
5402
|
168
|
90
|
125
|
184
|
156
|
234
|
273
|
75
|
125
|
|
|
6401
|
205
|
110
|
150
|
225
|
180
|
231
|
269
|
90
|
150
|
|
6402
|
236
|
132
|
200
|
259
|
210
|
270
|
315
|
110
|
150
|
|
575 V drive ratings (500 V to 575 V ±10%)
MODEL
|
NORMAL DUTY
|
HEAVY DUTY
|
|
MAXIMUM
CONT.
OUTPUT CURRENT
|
NOMINAL
POWER
AT 575V
|
MOTOR
POWER
AT 575V
|
PEAK CURRENT
|
MAXIMUM
CONT.
OUTPUT
CURRENT
|
OPEN LOOP PEAK CURRENT
|
CLOSED LOOP PEAK CURRENT
|
NOMINAL
POWER
AT 575V
|
MOTOR
POWER
AT 575V
|
|
|
|
A
|
kW
|
hp
|
A
|
A
|
A
|
A
|
kW
|
hp
|
|
|
3501
|
5.4
|
3.0
|
3.0
|
5.9
|
4.1
|
6.1
|
7.1
|
2.2
|
2.0
|
|
3502
|
6.1
|
4.0
|
5.0
|
6.7
|
5.4
|
8.1
|
9.4
|
3.0
|
3.0
|
|
3503
|
8.4
|
5.5
|
7.5
|
9.2
|
6.1
|
9.1
|
10.6
|
4.0
|
5.0
|
|
3504
|
11
|
7.5
|
10
|
12.1
|
9.5
|
14.2
|
16.6
|
5.5
|
7.5
|
|
3505
|
16
|
11
|
15
|
17.6
|
12
|
18
|
21
|
7.5
|
10
|
|
3506
|
22
|
15
|
20
|
24.2
|
18
|
27
|
31.5
|
11
|
15
|
|
3507
|
27
|
18.5
|
25
|
29.7
|
22
|
33
|
38.5
|
15
|
20
|
|
|
4603
|
36
|
22
|
30
|
39.6
|
27
|
40.5
|
47.2
|
18.5
|
25
|
|
4604
|
43
|
30
|
40
|
47.3
|
36
|
54
|
63
|
22
|
30
|
|
4605
|
52
|
37
|
50
|
57.2
|
43
|
64.5
|
75.2
|
30
|
40
|
|
4606
|
62
|
45
|
60
|
68
|
52
|
78
|
91
|
37
|
50
|
|
|
5601
|
84
|
55
|
75
|
92
|
63
|
93
|
108.5
|
45
|
60
|
|
5602
|
99
|
75
|
100
|
108
|
85
|
126
|
147
|
55
|
75
|
|
|
6601
|
125
|
90
|
125
|
137
|
100
|
128
|
149
|
75
|
100
|
|
6602
|
144
|
110
|
150
|
158
|
125
|
160
|
187
|
90
|
125
|
|
690 V drive ratings (500 V to 690 V ±10%)
MODEL
|
Normal Duty
|
Heavy Duty
|
|
MAXIMUM
CONT.
OUTPUT
CURRENT
|
NOMINAL
POWER
AT 690V
|
MOTOR
POWER
AT 690V
|
PEAK CURRENT
|
MAXIMUM
CONT.
OUTPUT
CURRENT
|
OPEN LOOP PEAK CURRENT
|
CLOSED LOOP PEAK CURRENT
|
NOMINAL
POWER
AT 690V
|
MOTOR
POWER
AT 690V
|
|
|
|
A
|
kW
|
hp
|
A
|
A
|
A
|
A
|
kW
|
hp
|
|
|
4601
|
22
|
18.5
|
25
|
24.2
|
19
|
27
|
31.5
|
15
|
20
|
|
4602
|
27
|
22
|
30
|
29.7
|
22
|
33
|
38.5
|
18.5
|
25
|
|
4603
|
36
|
30
|
40
|
39.6
|
27
|
40.5
|
47.2
|
22
|
30
|
|
4604
|
43
|
37
|
50
|
47.3
|
36
|
54
|
63
|
30
|
40
|
|
4605
|
52
|
45
|
60
|
57.2
|
43
|
64.5
|
75.2
|
37
|
50
|
|
4606
|
62
|
55
|
75
|
68.2
|
52
|
78
|
91
|
45
|
60
|
|
|
5601
|
84
|
75
|
100
|
92
|
63
|
93
|
108.5
|
55
|
75
|
|
5602
|
99
|
90
|
125
|
108
|
85
|
126
|
147
|
75
|
100
|
|
|
6601
|
125
|
110
|
150
|
137
|
100
|
128
|
149
|
90
|
125
|
|
6602
|
144
|
132
|
175
|
158
|
125
|
160
|
187
|
110
|
150
|
|
Inputs and Outputs
FUNCTION
|
QTY
|
I/O DEFAULT FUNCTION
|
RATING
|
Analog input 1
|
1
|
Frequency /speed ref 1
|
± 10V
|
Analog input 2
|
1
|
Frequency /speed ref 2
|
± 10V(default), 0-20mA or 4-20mA
|
Analog input 3
|
1
|
Motor thermistor
|
± 10V, 0-20mA, 4-20mA or Motor thermistor input (default)
|
Analog output
|
2
|
Speed/frequency
Torque (active current)
|
± 10V(default), 0-20mA or 4-20mA
|
Digital input
|
3
|
Run reverse input
Analog input 1/2 select
Jog forward input
|
+24V
|
Digital input / output
|
3
|
At zero speed output
Reset input
Run forward input
|
+24V
|
Relay
|
1
|
Drive OK indicator
|
Normally open
|
Drive enable (Safe Torque Off)
|
1
|
Safe Torque Off input
|
+24V
|
+24V External input
|
1
|
External 24V supply
|
+24V
|
Environmental safety and electrical conformance
IP20/Nema 1 rating, IP54 (NEMA 12) through panel mount
Ambient temperature -15 to +40°C, 50°C with derating
Humidity 95% maximum (non condensing) at 40°C
Altitude: 0 to 3000m, derate 1% per 100m between 1000m and 3000m
Vibration: Tested in accordance with IEC 60068-2-34
Mechanical Shock Tested in accordance with IEC 60068-2-27
Storage temperature -40°C to 50°C
Electromagnetic Immunity complies with EN 61800-3 and EN 61000-6-2
With onboard EMC filter, complies with EN 61800-3 (2nd environment)
EN 61000-6-3 and EN 61000-6-4 with optional footprint EMC filter
IEC 61000-3-4 Supply conditions
IEC 60146-1-1 Supply conditions
IEC 61800-5-1 (Power Drive Systems)
IEC 61131-2 I/O
EN 60529 Ingress protection
EN 50178 / IEC 62103 Electrical safety
Safe Torque Off (formally secure disable), independently assessed by BGIA to IEC 61800-5-2 SIL 3
EN 81-1 assessed by TÜV
EN 61000-6-2, EN 61000-6-4 EMC, UL508C, UL840
Dimensions, weights and ratings
SP CONTROL PLATFORM
|
Weight: 1.5kg (3.3lbs)
|
SP0 (£1.5kW)
|
Weight: 2.1kg (4.6lbs)
|
SP1 (£5.5kW)
|
Weight: 5kg (11lbs)
|
SP1405 / SP1406:
|
5.8kg (13lbs)
|
SP2 (£15kW)
|
Weight: 7kg (15.5lbs)
|
SP3 (£30kW)
|
Weight: 15kg (33lbs)
|
SP4 (£55kW)
|
Weight: 30kg (66lbs)
|
SP5 (£90kW)
|
Weight: 55kg (121lbs)
|
SP6 (£132kW)
|