Modul Typ
|
ADVT /
AAST /
ADIT
|
ADGT
|
AMDT /
ADFT
|
IOIT / OTOT / DIOT
|
Analog inputs |
|
Voltage and current ranges
|
± 156 mV .. ± 10 V / 0 .. 20 mA, 4 .. 20 mA |
— |
Galvanic isolation to system |
750 VDC |
750 VDC |
750 VDC |
— |
Max. differential voltage channel to channel |
110 V |
650 V |
100 V |
— |
Resolution |
24 bit |
24 bit |
14 bit |
— |
Analog outputs |
Resolution
|
16 bit |
— |
12 bit |
— |
Galvanic isolation |
750 V |
— |
100 V |
— |
Output |
0/4 .. 20 mA |
— |
0 .. 10 V |
— |
Max. burden / min. load |
650 Ω |
— |
2,5 KΩ |
— |
Digital inputs |
Galvanic isolation / input measurement range |
2.5 kV / low: 0 .. 1.5 VDC@0 .. 1.5 mA / high: 3.5 .. 90 VDC@2 mA |
Frequency / counter inputs |
Galvanic isolation / input measurement range |
2.5 kV / low: 0 .. 1.5 VDC@0 .. 1.5 mA / high: 3.5 .. 90 VDC@2 mA |
Measurement frequency |
up to 30 kHz (DIOT), up to 50 kHz (AMDT, ADFT) |
Digital outputs |
Galvanic isolation |
2.5 kV |
Switching voltage |
max. 50 VDC@2.5 A |
Data storage |
Internal |
4 .. 16 GB (approx. 40 million measurement values per GB / 300 million measurement values per GB for AMDT, ADFT) |
Interfaces |
Physical
COM 1 / COM 2 |
RS485, 9-pin Sub-D-sockets, DIN EN ISO 19245-1 |
Physical
COM 3 / COM 4 |
RS232, 9-pin Sub-D-plug |
Protocols COM 1 / COM 2 |
PROFIBUS DPV1 Slave (both interfaces), also reduntant, according to PNO 2.212 V1.2 |
Protocols COM 1 .. 4 |
Modbus RTU master / slave, customer-specific protocols, ASCII |
Ethernet |
RJ45 (8-pin STP socket), 1000Base-T, protocols: TCP/IP, HTTP, SMTP, NTP, Modbus TCP and OPC UA client / server |
PROFINET (optinal) |
2 x RJ45 (8-pin STP socket) for any topologies; conformance class CC-B; ring redundancy MRP |
WLAN (optional) |
802.11 b/g |
USB |
USB 2.0 type C for configuration and reading out stored data |
CAN |
9-pin Sub-D-socket, protocols: CAN RAW; baud rates: 50 k .. 1 MBaud |
Module bus baud rate / length |
1 MBaud / 10 m .. 25 kBaud / 100 m |
General technical information |
Dimensions / weight |
W 200 x H 73 x D 118 mm / 1 kg |
Fixing |
Rail mounting DIN EN 60715 or screw fixing |
Signal connection |
Detachable screw terminals, 33 terminals in 2 rows, lead protection, connecting cabling max. 2,5 mm² |
Display |
4 lines, operation via jog wheel |
Temperature range |
-20 .. 50 °C |
Supply voltage |
12 .. 24 VDC / ± 10 % |
Power input |
< 10 Watt |