• EchoPod® DL10 Ultrasonic Level Transmitter


    DOWNLOADS

     

    Application

    The general purpose ultrasonic level transmitter provides continuous level measurement up to 49.2" (1.25m) with a 4-20 mA signal output, and is configured via our free WebCal software. This non-contact liquid level sensor is ideally suited for corrosive, sticky or dirty liquids, and is broadly selected for small day tank, skid, IBC, sump and process tank level applications.

    Features

    • Continuous non-contact level measurement up to 49.2" (1.25m)
    •  
    • 4-20 mA output for longer signal distances up to 1000' (300m)

    • Narrow 2" beam width and short 2" dead band optimized for small tanks

    • Automatic temperature compensation for accurate measurement

    • PVDF transducer and 6P polycarbonate enclosure for corrosive liquids

    • Configuration is fast and easy via WebCal software and USB adapter

    Specifications

    Range: 49.2" (1.25m)
    Accuracy: 0.125" (3mm)
    Resolution: 0.019" (0.5mm)
    Dead band: 2" (5cm)
    Beam width: 2" (5cm)
    Configuration: WebCal® PC Windows® USB 2.0 USB 2.0
    Memory: Non-volatile
    Supply voltage: 24 VDC (loop)
    Consumption: 0.5W
    Loop resist.: 400Ω max
    Signal output: 4-20 mA, two-wire
    Signal invert: 4-20 mA or 20-4 mA
    Signal fail-safe: 4 mA, 20 mA, 21 mA,
    22 mA or hold last
    Process temp.: F: 20° to 140°
    C: -7° to 60°
    Temp. comp.: Automatic
    Ambient temp.: F: -31° to 140°
    C: -35° to 60°
    Pressure: MWP = 30 PSI (2 bar)
    Enclosure rating: Type 6P, encapsulated,
    corrosion resistant & submersible
    Encl. material: Polycarbonate
    Strain relief mat.: Santoprene
    Trans. material: PVDF
    Cable jacket mat.: Polyurethane
    Cable type: 4-conductor, shielded
    Cable length: 48" (1.2m)
    Process mount: 1" NPT (1" G)
    Mount gasket: Viton®
    Classification: General purpose
    Compliance: CE, RoHS
    Approvals: cFMus