White LED (User nonreplaceable parts. When replacement is required, contact your local distributor.)
Brightness Control
16 Levels (Adjusted with the touch panel or the software)
Backlight Service Life
50,000 hrs. or more (continuous operation at 25°C [77 °F] before backlight brightness decreases to 50%)
Language Fonts
Japanese: 6,962 (JIS Standards 1 & 2) (including 607 non-kanji characters) ANK: 158 (Korean fonts, Simplified Chinese and Traditional Chinese fonts are downloadable.)
Character Sizes
Standard font: 8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts, Stroke font: 6 to 127 pixel fonts, Image font: 8 to 72 pixel fonts
Font Sizes
Standard font: Width can be expanded up to 8 times. Height can be expanded up to 8 times.*1
Text
8 x 8 dots
100 char. x 75 rows
8 x 16 dots
100 char. x 37 rows
16 x 16 dots
50 char. x 37 rows
32 x 32 dots
25 char. x 18 rows
Control Memory
Variable Area
SRAM 64 KB (Replaceable Lithium battery for backup memory)
FLASH EPROM 32 MB (including a logic program area)
Data Backup
SRAM 320 KB (Replaceable Lithium battery for backup memory)
Clock Accuracy
±65 sec/month (deviation at room temperature and power is OFF)*3
Touch Panel Type
Resistive Film (analog)
Touch Panel Resolution
1,024 x 1,024
Touch Panel Service Life
1,000,000 times or more
Interface
Serial (COM1)
RS-232C Asynchronous Transmission Data Length: 7 or 8 bits, Parity: none, Odd or Even, Stop Bit: 1 or 2 bits, Data Transmission Speed: 2,400 bps to 115.2 kbps, Connector: D-Sub9 (plug)
Serial (COM2)
RS-422/485 Asynchronous Transmission Data Length: 7 or 8 bits, Parity: none, Odd or Even Stop Bit: 1 or 2 bits, Data Transmission Speed: 2,400 bps to 115.2 kbps, 187.5kbps (MPI) Connector: D-Sub9 (plug)
Ethernet (LAN)
IEEE802.3i/IEEE802.3u, 10BASE-T/100BASE-TX Connector: Modular jack (RJ-45) x 1
USB (TYPE-A)
Conforms to USB2.0 (TYPE-A) x 1, Power Supply Voltage: DC 5 V ±5 %, Output Current: 500 mA or less, Communication Distance: 5 m [16.4ft.] or less
USB (mini-B)
Conforms to USB2.0 (mini-B) x 1, Communication Distance: 5 m [16.4ft.] or less
SD Card
SD Card Slot x 1
Other font sizes can be set up with the Editor software.
Up to 60,000 steps can be converted in software. However, this reduces application memory capacity (for screen data) by 1 MB.
Depending on the operating temperature and age of unit, the clock can deviate from -380 to +90 sec/month. For systems where this level of deviation is a problem, the user should monitor and make adjustments when required.
General Specification
International Safety Standards
Rated Input Voltage
DC 24 V
Input Voltage Limits
DC 19.2 to 28.8 V
Allowable Voltage Drop
10 ms or less
Power Consumption
17 W or less
In-Rush Current
30 A or less
Voltage Endurance
AC 1,000 V 20 mA for 1 min (between charging and FG terminals)
Insulation Resistance
DC 500 V, 10 MΩ or more (between charging and FG terminals)
Surrounding Air Temperature
0 to 55 °C [32 to 131 °F]
Storage Temperature
-20 to 60 °C [-4 to 140 °F]
Ambient Humidity
10 to 90 % RH (Wet bulb temperature: 39 °C [102.2 °F] or less - no condensation.)
Storage Humidity
10 to 90 % RH (Wet bulb temperature: 39 °C [102.2 °F] or less - no condensation.)
Dust
0.1 mg/m³ (10-7 oz/ft³) or less (non-conductive levels)
Pollution Degree
For use in Pollution Degree 2 environment
Atmosphere
Free of corrosive gases
Air Pressure (altitude range)
800 to 1,114 hPa (2,000 m [6,561ft.] above sea level or less)
Vibration Resistance
IEC/EN61131-2 compliant, 5 to 9 Hz Single amplitude 3.5 mm [0.14 in.], 9 to 150 Hz Fixed acceleration: 9.8 m/s², X, Y, Z directions for 10 cycles (approx. 100 min)
Concussion Resistance
IEC/EN61131-2 compliant 147 m/s², X, Y, Z directions for 3 times
Functional grounding: Grounding resistance of 100Ω, 2mm² (AWG 14) or thicker wire, or your country's applicable standard. (Same for FG and SG terminals)
Structure
IP65f NEMA #250 TYPE 4X/13 (on the front panel when properly installed in an enclosure)*4
Cooling Method
Natural air circulation
Weight Approx.
2.5 kg [5.5 lb] or less (display unit only)
External Dimensions
W315x H241x D56 mm [W12.4 x H9.49 x D2.2 in.]
Panel Cut Dimensions
W301.5 x H227.5 mm [W11.87 x H8.96 in.], Panel thickness area: 1.6 to 5 mm [0.06 to 0.2 in.]*5
The front face of the GP unit, installed in a solid panel, has been tested using conditions equivalent to the standards shown in the specification. Even though the GP unit's level of resistance is equivalent to these standards, oils that should have no ef
Regarding dimensional tolerance, everything +1/-0 mm [+0.04/-0 in.] and R in angle are below R3 [R0.12 in.]. Even if the installation wall thickness is within the recommended range for the "Panel Cut Dimensions", depending on wall's material, size, and installation location of GP unit and other devices, the installation wall could warp. To prevent warping, the installation surface may need to be strengthened.
- Makes maintenance simple, even for equipment that is used for extended periods of time.
- Lets you save data even when using equipment that is left unpowered for long periods of time, giving peace of mind.
- It is recommended that batteries are replaced every 5 years. Batteries can be purchased as maintenance items.
No more accidental dropping
Special projections prevent the GP4000 series from being accidentally dropped through the hole when it is being installed in a panel.
Consistent direction of cabling
Thanks to a consistent connection direction for cables and other interfaces, routing of wiring is now simpler than ever.
Compatibility for easy replacement
Since the panel cutting dimensions are the same as conventional models, it is easy to replace only the display unit in an existing facility.
Easy to change the display screen
- The display screen can be changed by using a USB flash memory or SD card, without the need for a software license.
- The screen maintenance can be done without bringing a PC to a production site.
- A person in charge does not have to operate a PC, such as when manufacturing the multiple units of the same equipment.
Commercially available Type A to Mini-B USB cables can be used to transfer screen data.
Conforms to overseas standards for hassle-free export and use with overseas equipment
UL/cUL Hazardous Locations Class I, Division 2 Group A, B, C and D.
Acquired ATEX Zone 2/22 (Gas/Dust)
Acquired KCs (Korean Simple Explosion-proof)
Acquired NEPSI (Chinese Simple Explosion-proof)
Environment-Friendly
Energy Saving - Standard equipped with LED backlight LCD + Lighting adjustment
Energy-saving capabilities have been greatly improved. The GP4000 Series contributes to reducing on-site power consumption in a variety of ways including an on-board LED backlight in all models, and a lighting adjustment function used to decrease and eventually stand-by the display after being idle for a set period of time.
Easily connect multiple USB devices
A controller with serial interface, EZ Series accessory unit, bar code reader, and USB flash drive can be easily connected to the HMI unit.
When an error occurs, an operator can easily seek and check the condition on-site, just by touching the alarm message to call up various error-related data in chronological order. An alarm analysis screen with timing chart of alarm-related device addresses can be simply configured only through a few steps on GP-Pro EX software for easy troubleshooting, debugging and/or design changes of production equipment to reduce downtime for enhanced productivity.
Sampling Data - Collecting various data during production
Temperature, voltage, and other desired address values can be stored in the GP. Data and times can be confirmed on the sampling display.
Historical Trend Graph - Displaying data in an easy-to-see graph
The change in the collected data over time is displayed in an easy-to-understand form with a graph. The graph can be traced back to see the past data.
Operation Log - Recording the operator's operation
Operations are saved to a log, so you can see who did what, and when. The log can also be used for a trend analysis of erroneous operation of operators.
Enhanced Recipe Function
With the conventional recipe function, all recipe data must be stored at continuous addresses. The new recipe function allows writing random addresses and multiple data formats as a recipe.
CSV Data Transfer Function
Since the CSV data stored in the USB memory/SD card can be edited, the recipe data can easily be carried for performing updates on-site. The alarm message can be easily changed with CSV files only.
Internal Logic Program - Program with a familiar ladder language
- Screens and logic programming can be edited with the same software, so editing between parts and logic elements can be performed via drag and drop.
- Reduces PLC operation and program maintenance load.
- The online editing function allows you to make program changes on a computer during operation.
D-Script - Create unique macro program for user-customized data process and functions
Configure these settings based on trigger conditions including "Continuous Action", "Timer Bit Change", and "Condition Satisfied". Many functions are also provided including search (search and replace strings in the script) and debug functions (display messages and addresses on the unit).
D-Scripts created with GP-PRO/PBIII can be used unmodified so replacement is a breeze.
Network Solution
Pro-Server EX
Collect information of operation progress on a PC via Ethernet network. Download operating instructions, such as recipes, from an office PC to a GP.
* Purchase of a separate license is required.
GP-Viewer EX
The screen of the HMI on the site can be monitored from a PC at a remote location.
* Purchase of a separate license is required.
Web Server
Acquirable devices or alarms in the GP on the site can be monitored with a browser.
* Ethernet I/F models only
FTP-Server
The content of a USB memory or SD card attached to the GP on the site can be interchanged from a remote location.
* Ethernet I/F models only
RPA (Remote PC Access)
The work procedure document stored in a PC in an office can be displayed on the GP. This is effective to reduce procedural errors or other mistakes.
Pro-face HMIs support connection with a wide range of industrial controllers including PLCs, motion controllers, robots, and other devices.
A USB to RS-422/485 conversion adapter can be used to allow connection to a wide range of control equipment including temperature controllers, inverters, and PLCs.
For more information on supported equipment, please refer to this list.
Easy and flexible configuration of lamps and switches
Lamps can be configured in six colors with four lighting states in the screen editor software, GP-Pro EX.
EZ illuminated switches feature easily customizable insert labels.
* For example: HOME, Change Screen, Change, Speed, Run, Stop, Reset, Auto, Manual and etc...
The EZ fingerprint recognition unit can reduce problems or accidents caused by inappropriate password use.
Fingerprint data is registered and maintained through an HMI or PC connected to the fingerprint recognition unit.
* Fingerprint data for up to 100 users can be stored. * To purchase the EZ fingerprint recognition unit, contact to your local Pro-face distributor.
Using the remote monitoring and operation functions, actions that previously required multiple staff for a large-sized machine or long-distance application can be easily accomplished by fewer operators.
* Please check equipment status and maintain conditions for machine safety to avoid unintended equipment operation.
The Ethernet Multi-Link function allows you to easily add a GP as a sub-display to the facility without changing any settings of the control device.
Easily connect multiple USB devices
A controller with serial interface, EZ Series accessory unit, bar code reader, and USB flash drive can be easily connected to the HMI unit.
* EZ Fingerprint Recognition Unit also requires power supply cable. * Multiple devices of the same model cannot be connected.
Use Video for On-Site Adjustments with COGNEX In-Sight vision system communication driver
In combination with a COGNEX In-Sight vision system*1, the settings can be changed when watching images from the cameras on a GP unit on site.*2
A communication driver supports In-Sight Micro series and In-Sight 5000 series.
You can view video images from up to 3 cameras on a single screen. Up to 16 cameras can be connected to GP.Display position (X/Y), exposure time, focus, lighting and brightness can be adjusted on GP.
Supports Siemens PLC's tag import function
As the tag information of STEP7 Project Files created by Siemens PLC can be imported to GP-Pro EX screen data, you can reduce the man-hours for screen creation.
<Supported Data Type>
BOOL, BYTE, WORD, DWORD, SINT/USINT, INT/UINT, DINT/UDINT, REAL, STRING, ARRAY, STRUCTURE, TIME, TIME_OF_DAY, DATE, DATE_AND_TIME