Transducer Power: |
5 Vdc 120 mA (max 8 cells in 350 Ohm in parallel) |
Measuring range: |
From -3.9 to +3.9 mV / V |
Input sensitivity: |
0.02 microV / division |
Linearity: |
<0.01% of the full scale |
Thermal Drift: |
<0.0003% of the full scale / ° C |
A / D converter: |
24 bit |
Internal Resolution: |
> 16,000,000 points |
Viewable resolution: |
99,999 divisions that can be viewed on net weight |
Decimal settings: |
0.0; 0.00; 0.000; 0.0000 |
Filter: |
Selectable from 0.2 to 25 Hz |
Power Supply: |
230 Vac ± 10% - 50/60 Hz power consumption 7 W (115 Vac on request) |
Operating Temperature: |
-10 ÷ + 50 ° C (85% max humidity without condensation) |
Storage Temperature: |
-20 ÷ + 70 ° C |
Logic Outputs: |
4 relays (NO contact) Max. 115 Vac / 30 Vdc 0.5 A cad. |
Logic Inputs: |
3 optocoupled at 12 Vdc / 24 Vdc PNP |
Serial port: |
COM1: RS232 half duplex COM2: RS422 / RS485 half duplex |
Transmission distance: |
15m (RS232C), 1000m (RS422 and RS485) |
Protocol: |
ASCII, Modbus, Custom Printers P190 or FT190, EPSON |
Baud rate: |
From 300 to 115200 (selectable) |
Compliance with regulations: |
EN61000-6-3, EN1000-6-2, EN61010-1 |
Insulation: |
Class II |
Size: |
144 x 72 x 120 mm (L x H x D) |
Drilling template: |
139 x 67 mm (L x H) |
Electric connections: |
Extractable screw terminals 5.08 mm |
Optional dosing software: |
1 component loading or unloading up to 50 programmable recipes |
Optional analog output: |
Optocolted at 16 Bit Voltage: 0 ÷ 5 or 0 ÷ 10V (R> 10K Ohm); Current: 0 ÷ 20 or 4 ÷ 20mA (R <300 Ohms); Linearity: 0.03% of the scales |
Optional BCD output: |
Through external modules |
Optional Profibus Output: |
Through external module |
Continuous power supply: |
12 Vcc; Available analog voltage output is 0 ÷ 5 V; Analog current output with R <260 Ohms; 24 Vcc |