Technical specifications

ProfiMessage / ProfiLab
Analog inputs
Module type ADVT / AAST / ADIT ADGT    AMDT / ADFT    
Voltage and current measurement range ± 156 mV .. ± 10 v etc.
Sensors mV, mA, Thermocouples, RTD (RTD except ADVT) mV, mA
Potential isolation to system 750 VDC
Potential isolation channels 110 V 650 V 100 V
Resolution 24 Bit 14 Bit
Measurement accuracy

V / mA: 0,1 %

RTD100: 0.1 K

RDT000: 0.05 K

Thermoelemente: 0.1 % EW

0.1 %

-

-

-

Analog outputs

Resolution

16 Bit - 12 Bit
Potential isolation 750 V - 100 V
Output 0/4 .. 20 mA - 0 .. 10 V
Max. load / min. load 650 Ω - 2.5 kΩ
Digital inputs
Potential isolation 2.5 kV
Input measurement range low: 0 .. 1.5 VDC@0 .. 1.5 mA / high: 3.5 .. 90 VDC@2 mA
Frequency / counter inputs
Potential isolation / input measurement range 2.5 kV / low: 0 .. 1.5 VDC@0 .. 1.5 mA / high: 3.5 .. 90 VDC@2 mA
Measurement frequency bis 30 kHz bei TTL-Pegel
Digital outputs
Potential isolation 2.5 kV
Switching voltage max. 50 VDC@2.5 A
Data storage
Standard size / measurment values Storage partitionable as required, standard: 500 MB/  max. 32 million measurement values
Max. size / measurement values 15.5 GB / up to 1 billion measurement values (7 billion measurement values for AMDT, ADFT)
Interfaces
Physical equipment COM 1 / COM 2 RS485, 9-pole sub-D-plug, DIN EN ISO 19245-1
Physical equipment COM 3 / COM 4 RS232, 9-pole sub-D plugs
Protocols COM 1 / COM 2 PROFIBUS DPV1 Slave (both interfaces), incl. redundancy according to PNO 2.212 V1.2
Protocols COM 3 / COM 4 Modbus RTU master / slave, customer-specific protocols
Ethernet RJ45 (8-pole STP-plug), 100 Base-TX; Protocols: TCP/IP, HTTP, SMTP, NTP, Modbus TCP Client / server
USB USB 1.1. for configuration and data memory read out
CAN 9-pole sub-D plug, Protocols: CAN, RAW; baud rates: 50 k .. 1 MBaud
Module bus
Mechanical type 3-pole Phoenix connector; inetrnal bus to connect additional modules
Baud rate / length 1 MBaud (adjustable) / up to 10 m (1 MBaud)
General technical information
ProfiMessage dimension / weight 200 x 73 x 118 mm  / 1 kg
ProfiMessage fixing Rail mounting DIN EN 60715 or screw fixing
ProfiMessage signal connections Detachable screw terminals, 33 terminals in 2 rows, lead protection, connecting cabling max. 2.5 mm²
ProfiLab dimension / weight 226 x 145 x 180 mm / 1 kg
ProfiLab signal connections Up to 64 4 mm lab plugs, gold-plated
Temperature range -20 .. 60 °C
Power supply 12 .. 36 VDC / 12 .. 28 VAC eff. / ± 10 %, at AMDT/ADFT min. 18 VAC/DC
Power input < 10 Watt
 
 
 

 