Features Functions Versions Specifications Software
 
Module type
(2 modules per master / slave)
ADVT / AAST / ADIT ADGT IOIT / OTPT / DIOT
Analog inputs 15 / 4 / 10 8 -
Sensors mv, mA, Thermocouples, RTD
(RTD except ADVT)
mv, mA, Thermocouples, RTD -
Total sampling rate 600 Hz 60 Hz -
Voltage measurement range 156 mV .. 10 V, ± 156 mV .. ± 10 V / 0 .. 20 mA, 4 .. mA, ± 20 mA -
Galvanic isolation to system 750 VDC 400 VDC -
Galvanic isolation channel to channel 110 VDC 650 VDC -
Resolution/Type ADC 24 bit Sigma-Delta 24 bit Sigma-Delta -
Measurement accuracy Voltage, current: 0.01 % of the measuring range end value
Thermocouples: 0.1 % of measuring range after sensor compensation*
-
Measuring accuracy Pt 100
(4-wire connection)
Measuring range -260 °C to 147 °C: 0.10 °C
Measuring range -260 °C to 596 °C: 0.20 °C
Measuring range -260 °C to 849 °C: 0.43 °C
-
Measuring accuracy Pt 1000
(4-wire connection)
Measuring range -260 °C to 64 °C: 0.10 °C
Measuring range -260 °C to 408 °C: 0.15 °C
Measuring range -260 °C to 849 °C: 0.35°C
-
Analog outputs - / 4 / 1 - -
Resolution 16 bit - -
Potential isolation 750 V - -
Output 0/4 .. 20 mA - -
Min. load / max. burden 650 Ω - -

* These measuring accuracies apply to positive measuring temperatures (> 0°C). For measurements in the negative temperature range, we recommend calibration at the respective operating point.

 
Module type
(2 modules per master / slave)
ADVT / AAST / ADIT ADGT IOIT / OTPT / DIOT
Digital inputs - / 2 / - - 24 / 1 / 12
Thereof with frequency measurement / counting function - / - / - - - / - / 11
Max. measurement frequency - / - / - - - / - / 30 kHz
Input measurement range low: 0 .. 1.5 VDC@0 ... 1.5 mA / high: 4.8 ... 90 (ProfiLab: 50)
VDC@ 2.5 .. 3.5 mADC
Potential isolation 2.5 kV
Digital outputs - / 2 / 1 - 1 / 24 / 16
Potential isolation 2.5 kV
Switching voltage max. 50 VDC@2.5 A
Data storage
Internal 0.5 .. 15.5 GB (approx. 30 million mesurement values per GB)
 
 
Module type
(2 modules per master / slave)
ADVT / AAST / ADIT ADGT IOIT / OTPT / DIOT
Interfaces
Physical equipment COM 1 / COM 2 RS485, 9-pole sub-D socket, IEC 61158-2
Physical equipment COM 3 / COM 4 RS232, 9-pole sub-D-socket (COM 3), 9-pole sub-D plug (COM 4)
Protocols COM 1 / COM 2 PROFIBUS DPV1 slave (both interfaces), also redundant according to PNO 2.212 V1.2
Protocols COM 1 .. COM 4 Modbus RTU master / slave, customer-specific protocols, ASCII
TCP/IP RJ45 (8-pin STP socket), 1000Base-T; protocols: TCP/IP, HTTP, SMTP, NTP, Modbus TCP Client (optional) / Server, OPC UA Client / Server, OPC UA HA Server (optional)
USB USB 1.1 for reading out stored data
CAN 9-pole sub-D socket, Protocols: CAN, RAW; baud rates: 25 k .. 1 MBaud; dbc-import possible
Module bus baud rate / length 1 MBaud / 10 m ... 25 kBaud / 100m
General technical information
ProfiMessage dimensions / weight W 200 x H 73 x D 137 mm / 1 kg
ProfiMessage mounting Mounting rail DIN EN 60715 or screw mounting
ProfiMessage signal connections Detachable screw terminals, 33 terminals in 2 rows, lead protection, connecting cabling max. 2.5 mm²
ProfiLab dimensions W 226 x H 145 x D 180 mm
ProfiLab signal connections up to 64 pieces 4 mm laboratory sockets, gold-plated
Temperature range -20 .. 50 °C
Humidity max. 90 % relative humidity, non-condensing
Supply voltage 12 .. 36 VDC / 12 .. 28 VAC rms / ± 10 %
Power input < 10 watts
 
 

 