Voltage, current: 0.01 % of the measuring range end value Thermocouples: 0.1 % of measuring range after sensor compensation*
-
Measuring accuracy Pt 100 (4-wire connection)
Measuring range -260 °C to 147 °C: 0.10 °C Measuring range -260 °C to 596 °C: 0.20 °C Measuring range -260 °C to 849 °C: 0.43 °C
-
Measuring accuracy Pt 1000 (4-wire connection)
Measuring range -260 °C to 64 °C: 0.10 °C Measuring range -260 °C to 408 °C: 0.15 °C Measuring range -260 °C to 849 °C: 0.35°C
-
Analog outputs
- / 4 / 1
-
-
Resolution
16 bit
-
-
Potential isolation
750 V
-
-
Output
0/4 .. 20 mA
-
-
Min. load / max. burden
650 Ω
-
-
* These measuring accuracies apply to positive measuring temperatures (> 0°C). For measurements in the negative temperature range, we recommend calibration at the respective operating point.
Module type (2 modules per master / slave)
ADVT / AAST / ADIT
ADGT
IOIT / OTPT / DIOT
Digital inputs
- / 2 / -
-
24 / 1 / 12
Thereof with frequency measurement / counting function