LED ON / OFF control, adjustable screen saver activation time
Brightness Adjustment
16 levels of adjustment available via touch panel in the configuration menu
Language Fonts *1
Japanese, ASCII, Chinese (Simplified), Chinese (Traditional), Korean, Cyrillic, Thai
Character Sizes
8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts
Font Sizes
Width can be expanded 1 to 8 times. Height can be expanded 1/2 and 1 to 8 times.
8 x 8 pixels
40 characters per row x 30 rows
8 x 16 pixels
40 characters per row x 15 rows
16 x 16 pixels
20 characters per row x 15 rows
32 x 32 pixels
10 characters per row x 7 rows
Memory
Application Memory
When using GP-Pro EX:
Media: FLASH EPROM
Screen Area *2: 16MB
User Font Area: 8MB
Logic Program Area: 132KB (Equivalent to 15,000 steps)*3
Free Space: None
Removable System: None
Backup Memory
When using GP-Pro EX:
Screen Area: nvSRAM 128KB
Variable Area: nvSRAM 64KB
Battery: Memory / Primary battery for clock data backup (Send back for replacement)
Touch Panel
Type
Resistive Film (analog)
Lifetime
1 million touches or more
Interface
Serial (COM1)
RS-232C/RS485 x 1
RS-232C (Connector type: RJ45, Isolation: None, Maximum baud rate: 115,200 bps, Cable Type: Shielded, Cable Maximum length: 15 m (49 ft), 5 Vdc power supply for RS-232C: None)
RS-485 (Connector type: RJ45, Isolation: None, Maximum baud rate: 115,200 bps, Cable Type: Shielded, Cable Maximum length: 200 m (656 ft), Polarization: Setting is required via software when connecting Multiple LTs. Refer to the "GP-Pro EX Device/ PLC Manual" for the setting. 5 Vdc power supply for RS-485: None) *4
CANopen (Master)
CAN-CiA (ISO 11898-2:2002 Part 2), Connector: D-sub9 (pin)
Ethernet
IEEE802.3 compliant Ethernet x 1
(Connector type: RJ45, Driver: 10 M half duplex (auto negotiation)/ 100 M full duplex (auto negotiation), Cable type: Shielded, Automatic cross-over detection: Yes)
USB (Type A)
USB 2.0 (Type A) x 1
(Power Supply Voltage: 5Vdc +/-5%, Maximum Current Supplied: 500mA, Maximum Transmission Distance: 5m (16.4 ft.))
USB (Mini-B)
USB 2.0 (Mini-B) x 1
Control
DIO (Source Type)
12 Points Standard Input (including 2 Points for Fast Input)
6 Points Standard Output, 2 Points for Fast Output
AIO
2ch analog inputs (13-bit) and 2ch analog inputs (16-bit) for Thermocouple
2ch analog outputs (12-bit)
*2Use the screen area when the user font area's capacity is exceeded - for example, when an image font or a picture font is used.
*3Up to 60,000 steps can be converted in software. However, this reduces application memory capacity (for screen data) by 1 MB.
*42-wire connection is available for RS-485. When a Device/PLC supports 2-wire connection, 4 wires (RXD+, TXD+, RXD-, and TXD-) can be short-circuited to be 2 wires (RXD+ and TXD+ = D1, RXD- and TXD- = D0). For details on the connection, refer to the connection manual.
General Specifications
International Safety Standards
Rated Input Voltage
24 Vdc
Input Voltage Limits
20 to 28.8 Vd
Acceptable Voltage Drop
10 ms or less at 20.4 Vdc
Power Consumption
13 W or less
In-Rush Current
30 A or less at 28.8 Vdc
Voltage Endurance between power terminal and frame ground (FG)
500 Vdc for 1 minute
Insulation Resistance between power terminal and FG
10 MΩ or higher at 500 Vdc
Environmental Specifications
Standard compliance
IEC 61131-2
Ambient operating temperature for the display and the rear module
Horizontal installation
0 to 50°C (32 to 122°F)
Vertical installation
0 to 40°C (32 to 104°F)
Storage temperature
- 20 to 60°C (- 4 to 140°F)
Storage altitude
0 to 10,000 m (0 to 32,808 ft)
Operating altitude
0 to 2,000 m (0 to 6,560 ft)
Surrounding Air and Strage Humidity
5 to 85% w/o condensation (non-condensing, wet bulb temperature 39°C (102.2°F) or less)
Degree of pollution
IEC60664
2
Degree of protection
IEC61131-2
IP20 with protective covers in place
Corrosive gases
Free of corrosive gases
Dust
≤0.1 mg/m3 (10-7 oz/ft3) (non-conductive levels)
Atmospheric pressure (Operating Altitude)
800 to 1,114 hPa (2000 m (6,561 ft) or lower)
Vibration resistance
Mounted on a DIN rail
3.5 mm (0.138 in.) fixed amplitude from 5 to 8.4 Hz
9.8 m/s2 (1 gn) fixed acceleration from 8.4 to 150 Hz
Mounted on a panel
3.5 mm (0.138 in.) fixed amplitude from 5 to 8.6 Hz
9.8 m/s2 (1 gn) fixed acceleration from 8.6 to 150 Hz
Mechanical shock resistance
Mounted on a DIN rail
147 m/s2 (15 gn) for a duration of 11 ms
Mounted on a panel
147 m/s2 (15 gn) for a duration of 6 ms
Electrostatic discharge
IEC/EN 61000-4-2
8 kV (air discharge)
6 kV (contact discharge)
Rediated radio frequency electromagnetic fields
IEC/EN 61000-4-3
10 V/m (80 MHz to 3 GHz)
Fast transients / Burst noise
IEC/EN 61000-4-4
Power lines: 2 kV
Digital I/O: 1 kV
Relay outputs: 2 kV
Ethernet line: 1 kV
COM line: 1 kV
CAN line: 1 kV
Surge immunity
IEC/EN 61000-4-5
Power supply: CM: 1 kV; DM: 0.5 kV
Digital I/O: CM: 1 kV; DM: 0.5 kV
Shielded cable: 1 kV
CM = common drive
DM = differential drive
Conducted disturbances induced by radio-frequency fields
IEC/EN 61000-4-6
10 Veff (0.15 to 80 MHz)
Mains terminal dusturbance voltage
EN 55011 (IEC/CISPR11)
150 to 500 kHz, quasi peak 79 dBμV
500 kHz to 30 MHz, quasi peak 73 dBμV
Electric field strength
EN 55011 (IEC/CISPR11)
30 to 230 MHz, quasi peak 10 m @40 dBμV/m
230 MHz to 1 GHz, quasi peak 10 m @47 dBμV/m
Vibration immunity (operating)
IEC 61131-2
Protection structure
NEMA TYPE 4X (indoors, with panel embedded)
Protection (front module)
IP65f - (IEC 60529)
Protection (rear module)
IP 20 - (IEC 60529)
Shock immunity (operating)
IEC 61131-2
15 gn 11 ms
Cooling method
Natural air circulation
Weight
784 g (27.65 oz)
Color
Front module: PT404 Rear module: RAL 7032
Material
Front module: PAA+GF
Rear module: PC/PBT
Digital Inputs
Digital Input Characteristics
Rated Current
5 mA
Inrush Values
Voltage
30 Vdc
Current
6.29 mA max.
Input impedance
4.9 kΩ
Input type
Sink/Source
Rated voltage
24 Vdc
Maximum Allowable Voltage
28.8 Vdc
Input limit values
ON Voltage
15 Vdc or more (15 to 28.8 Vdc)
OFF Voltage
5 Vdc or less (0 to 5 Vdc)
ON Current
2.5 mA or more
OFF Current
1.0 mA or less
Isolation
Method
Photo coupler Isolation
Between internal logic
500 Vdc
Filtering
0.5 ms x N (N is 0 to 63)
IEC61131-2 edition 3 type
Type 1
Compatibility
Supports 2 wire and 3 wire sensors
Cable type and length
Shielded: Maximum 100 m (328 ft)
Non-shielded: 50 m (164 ft)
Terminal blocks
Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable
Input paralleling
No
* I0 and I1 are Fast input terminals and can be also used as a Standard input. For specifications, see the specifications of Fast Input.
High Speed Counter Input Characteristics
Rated Current
Voltage
24 Vdc
Current
7.83 mA
Inrush values
Voltage
30 Vdc
Current
9.99 mA
Input impedance
3.2 kΩ
Input type
Sink/Source
Rated voltage
24 Vdc
Maximum Allowable Voltage
28.8 Vdc
Input limit values
ON Voltage
15 Vdc or more
OFF Voltage
5 Vdc or less
ON Current
5 mA or more
OFF Current
1.5 mA or less
Isolation
Method
Photo coupler Isolation
Between channels logic
500 Vdc
Filtering
None, 4 μs, 40 μs
IEC61131-2 edition 3 type
Type 1
Compatibility
Supports 2 wire and 3 wire sensors
Cable
Type
Shielded
Length
Maximum 10 m (33 ft)
Terminal blocks
Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable
Maximum frequency
· 100 kHz is the maximum frequency for Single-phase
· 50 kHz is the maximum frequency for 2-phase
· Duty Rate: 45 to 55%
Caution: Q0 and Q1 circuits are push-pull circuits. The following is the operation of the push-pull circuit at the Sink Output and the Source Output.
Sink Output: +24(V) is output to terminal Q0, Q1 when the logic for Q0, Q1 is off
Source Output: 0(V) is output to terminal Q0, Q1 when the logic for Q0, Q1 is off
Standard Output terminals Q2 or later are common open collector outputs.
Do not connect Fast Output terminals Q0, Q1 and Standard Output terminals Q2 or later. It will short.
If you add a manual circuit to terminal Q0, Q1, isolate the manual circuit and terminal Q0, Q1 with a relay. Without isolation, it will short.
Between power supply port and protective earth ground (PE) = 500 Vdc
10 MΩ or more
Residual voltage
for I = 0, 1 A
1.5 Vdc or less
Delay
Off to on (50 mA load): 1.1ms
On to off (50 mA load): 1.1ms
NOTE: The delay is not including the cable delay.
Minimum load impedance
80 Ω
Maximum Pulse output frequency
50 KHz
Maximum PWM output frequency
65 kHz
Accuracy
Pulse Output/PWM Output
Frequency
Accuracy
Duty
10 to 100 Hz
0.1%
0 to 100%
10 to 1000 Hz
1%
1 to 99%
1.001 to 20 kHz
5%
5 to 95%
20.001 to 45 kHz
10%
10 to 90%
45.001 to 65 kHz
15%
15 to 85%
Duty rate range
1 to 99%
Cable
Type
Shielded, including 24 Vdc power supply
Length
Maximum 5 m (16 ft)
Terminal blocks
Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable
NOTE: When using the acceleration/deceleration pulse output, there is a 1% maximum error for the frequency.
Caution: Q0 and Q1 circuits are push-pull circuits. The following is the operation of the push-pull circuit at the Sink Output and the Source Output.
Sink Output: +24(V) is output to terminal Q0, Q1 when the logic for Q0, Q1 is off
Source Output: 0(V) is output to terminal Q0, Q1 when the logic for Q0, Q1 is off
Standard Output terminals Q2 or later are common open collector outputs.
Do not connect Fast Output terminals Q0, Q1 and Standard Output terminals Q2 or later. It will short.
If you add a manual circuit to terminal Q0, Q1, isolate the manual circuit and terminal Q0, Q1 with a relay. Without isolation, it will short.
Analog Inputs and Analog Outputs
Analog Input Characteristics
Characteristic
Voltage input
Current input
Number of maximum input
2
Input type
Single-ended
Input range
-10 to 10 Vdc/0 to 10 Vdc
0 to 20 mA/4 to 20 mA
Input impedance
1 MΩ or more
250 ± 0.11% Ω
Sample duration time
10 ms per channel + 1 scan time
Total input system transfer time
20 ms + 1 scan time
Input tolerance
Maximum deviation
at 25°C (77°F)
without
electromagnetic
disturbance
± 1% of the full scale
Maximum deviation
± 2.5% of the full scale
Digital resolution
13 bits
Temperature drift
± 0.06% of the full scale
Common mode characteristics
80 db
Cross talk
60 db
Non-linearity
± 0.4% of full scale
Input value of LSB
5 mV
10 μΑ
Maximum allowed overload (no
damages)
± 30 Vdc (less than
5 minutes)
± 15 Vdc (No damage)
± 30 mA dc
Protection type
Photo coupler between input and internal circuit
Cable
Type
Shielded
Length
Must be less than 3 m for IEC61131-2 conformance. Maximum transmission distance is 10m.
Terminal blocks
Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable
Isolation
External input: Photo-coupler isolation
Between channels: Non-isolated
Temperature Input (Temperature Probes) Characteristics
Input sensor type
Pt100/Pt1000/Ni100/Ni1000
Input temperature range
Pt100/Pt1000: -200 to 600°C (-328 to 1112°F)
Ni100/Ni1000: -20 to 200°C (-4 to 392°F)
Measuring current
Pt100/Ni100
1.12 mA ± 3.5%
Pt1000/Ni1000
0.242 μA ± 3.5%.
Input impedance
Typically 10 MΩ
Sample duration time
10 ms+1 cycle time
Wiring type
2-wire or 3-wire connection configured by software
for all inputs
Conversion mode
Sigma delta type
Input filter
Low pass
Resolution temperature value
0.1°C (0.18°F)
Detection type
Open circuit (detection on each channel)
Input tolerance*
Maximum
deviation at 25°C
(77°F) without
electromagnetic
disturbance
± 5°C (41°F)
Maximum
deviation at
25 to 50°C
(77 to 122°F)
Pt type: ± 5.6°C (42.08°F)
Ni type: ± 5.2°C (41.36°F)
Temperature drift
30 ppm/°C
Digital resolution
16 bits
Rejection in
differential mode
50/60 Hz
Typically 60 dB
Common mode
rejection
Typically 80 dB
Isolation Method
Photo coupler Isolation
Permitted input signal
±5 Vdc max.
Cable length
Pt100/Ni100
20 Ω or less
Pt1000/Ni1000
200 Ω or less
Terminal blocks
Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable
Noise resistance - cable
Shielded cable is necessary
* Excluding errors caused by the wiring
Temperature Input (Thermocouple) Characteristics
Input sensor type
Thermocouple
Input type range(1)
J (-200 to 760°C) (-328 to 1400°F)
K (-240 to 1370°C) (-400 to 2498°F)
R (0 to 1600°C) (32 to 2912°F)
B (200 to 1800°C) (392 to 3272°F)
S (0°C to 1600°C) (32 to 2912°F)
T (-200 to 400°C) (-328 to 752°F)
E (-200 to 900°C) (-328 to 1652°F)
N (-200 to 1300°C) (-328 to 2372°F)
Input impedance
Typically 10 MΩ
Sample duration time
10 ms+1 cycle time
Conversion mode
Sigma delta type
Digital resolution
16 bits
Input filter
Low pass
Resolution temperature value
0.1°C (0.18°F) (Type J)
Detection type
Open circuit (detection on each channel)
Input tolerance
Maximum deviation at
25°C (77°F) without
electromagnetic
disturbance
0.2 % of the full scale, plus standard point of compensation precision at +/- 6°C.
Maximum deviation
0.28 % of full scale range
Temperature drift
30 ppm/°C
Input tolerance - terminal temperature
compensation
± 5°C (41°F) after 10 min.
Cold junction compensation in the
temperature range (0 to 50°C (122°F))