Ratings
|
NORMAL DUTY [3]
|
HEAVY DUTY [3]
|
|
COMPACT WIDTH (mm)
|
ORDER
CODE
|
MAX
CONT. CURRENT (A)
|
TYPICAL MOTOR OUTPUT
@ 400V (kW)
|
TYPICAL MOTOR OUTPUT
@ 460V (hp)
|
MAX
CONT. CURRENT (A)
|
TYPICAL MOTOR OUTPUT
@ 400V (kW)
|
TYPICAL MOTOR OUTPUT
@ 460V(hp)
|
DRIVE ONLY
|
WITH SWITCH
DIS -
CONNECTOR
|
380-480Vac +/-10-%
|
400
|
400
|
SP64x1
|
205
|
110
|
150
|
180
|
90
|
150
|
SP64x2
|
236
|
132
|
200
|
210
|
110
|
150
|
SP74x1
|
290
|
160
|
250
|
238
|
132
|
200
|
SP74x2[4]
|
350
|
200
|
250
|
290
|
160
|
250
|
800
|
SP84x1
|
389
|
225
|
300
|
335
|
185
|
250
|
SP84x2
|
450
|
250
|
400
|
389
|
225
|
300
|
SP84x3
|
545
|
315
|
450
|
450
|
250
|
350
|
SP84x4
|
620
|
355
|
500
|
545
|
315
|
400
|
800
|
1200
|
SP94x0
|
690
|
400
|
600
|
593
|
315
|
500
|
SP94x1
|
690
|
400
|
600
|
620
|
355
|
500
|
SP94x3
|
900
|
500
|
800
|
790
|
450
|
700
|
SP94x4
|
1010
|
560
|
900
|
900
|
500
|
800
|
SP94x5
|
1164
|
675
|
1000
|
1010
|
560
|
900
|
1200
|
Not Available
|
SP94x5
+ 1 x SP94x5
Ext,
|
1746
|
960
|
1500
|
1515
|
830
|
1250
|
1600
|
SP94x5
+ 2 x SP94x5
Ext.
|
2328
|
1280
|
2000
|
2020
|
1110
|
1750
|
2000
|
SP94x5
+ 3 x SP94x5
Ext.
|
2910
|
1600
|
2500
|
2525
|
1380
|
2150
|
Ratings shown are for IP21 at 40°C ambient or IP23 at 30°C ambient, 3kHz switching frequency and 1000m altitude.Ratings shown are for IP21 (NEMA 1) at 40°C ambient or IP23 at 30°C ambient, 3kHz switching frequency and 1000m (3,300ft) altitude.
|
|
|
|
NORMAL DUTY [3]
|
HEAVY DUTY [3]
|
|
COMPACT WIDTH (mm)
|
ORDER
CODE
|
MAX
CONT.
CURRENT (A)
|
TYPICAL MOTOR OUTPUT
@ 690V (kW)
|
TYPICAL
MOTOR OUTPUT
@ 575V (hp)
|
MAX
CONT. CURRENT (A)
|
TYPICAL MOTOR OUTPUT
@ 690V (kW)
|
TYPICAL MOTOR OUTPUT
@ 575V (hp)
|
DRIVE
ONLY
|
WITH SWITCH
DIS -
CONNECTOR
|
500-690Vac +/-10-% |
400
|
400
|
SP66x1
|
125
|
110
|
125
|
100
|
90
|
100
|
SP66x2
|
144
|
132
|
150
|
125
|
110
|
125
|
SP76x1
|
168
|
160
|
150
|
144
|
132
|
150
|
SP76x2
|
192
|
185
|
200
|
168
|
160
|
150
|
800
|
SP86x1
|
231
|
200
|
250
|
186
|
185
|
200
|
SP86x2
|
266
|
225
|
300
|
231
|
200
|
250
|
SP86x3
|
311
|
315
|
350
|
266
|
250
|
300
|
SP86x4
|
355
|
355
|
400
|
311
|
315
|
350
|
800
|
1200
|
SP96x0
|
403
|
400
|
450
|
350
|
315
|
400
|
SP96x1
|
400
|
400
|
450
|
347
|
355
|
400
|
SP96x3
|
533
|
500
|
600
|
466
|
450
|
500
|
SP96x4
|
616
|
560
|
700
|
533
|
500
|
600
|
SP96x5
|
711
|
630
|
800
|
622
|
560
|
700
|
1200
|
Not Available
|
SP96x5
+ 1 x SP96x5 Ext.
|
1067
|
960
|
1150
|
933
|
830
|
1000
|
1600
|
SP96x5
+ 2 x SP96x5 Ext.
|
1422
|
1280
|
1550
|
1244
|
1120
|
1350
|
2000
|
SP96x5
+ 3 x SP96x5 Ext.
|
1778
|
1600
|
1950
|
1555
|
1380
|
1700
|
Ratings shown are for IP21 (NEMA 1) at 40°C ambient or IP23 at 30°C ambient, 3kHz switching frequency and 1000m (3,300ft) altitude.
Normal Duty |
Suitable for most applications, current overload of 110% for 165 seconds is available. Where motor rated current is less than the drive rated continuous current, higher overloads are achieved. |
Heavy Duty |
Suitable for demanding applications, current overload of up to 150% for 60 seconds |
Environmental Safety and Electrical Conformance
Humidity 95% maximum (non condensing) at 40°C
Altitude: 0 to 3000m, derate 1% per 100m between 1000m and 3000m
Vibration: Drive Modules tested in accordance with IEC 60068-2-34
Mechanical Shock Tested: Drive Modules in accordance with IEC 60068-2-27
Storage temperature: -40°C to 50°C
Electromagnetic Immunity complies with EN 61800-3 and EN 61000-6-2
With on board EMC filter, complies with EN 61800-3 (2nd environment)
EN61000-6-4 with optional EMC filter (contact the supplier of your drive)
IEC 60146-1-1 General requirements
IEC 61800-5-1 Safety of Power Drive Systems
IEC 61131-2 I/O
EN 60529 Ingress protection
Safe Torque Off (Secure Disable) meets EN 954-1-cat3
UL508C (except drives with switch disconnector and IP23 drives)
CSA C22.2 no 14-05
IP21 (NEMA 1) cabinet design, optional IP23 (IP23 option not UL approved)
Dimensions and weights