LED ON / OFF control, adjustable screen saver activation time
Brightness adjustment
16 levels of adjustment available via touch panel in the configuration menu
Language Fonts *1
Japanese, ASCII, Chinese (Simplified), Chinese (Traditional), Korean, Cyrillic, Thai
Character sizes
8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts
Font sizes
Width can be expanded 1 to 8 times. Height can be expanded 1/2 and 1 to 8 times.
8 x 8 pixels
40 characters per row x 30 rows
8 x 16 pixels
40 characters per row x 15 rows
16 x 16 pixels
20 characters per row x 15 rows
32 x 32 pixels
10 characters per row x 7 rows
Memory
Application Memory
When using GP-Pro EX:
Media: FLASH EPROM
Screen Area *2: 16MB
User Font Area: 8MB
Logic Program Area: 132KB
*3 (Equivalent to 15,000 steps)
Free Space: None
Removable System: None
Backup Memory
When using GP-Pro EX:
Screen Area: nvSRAM 128KB
Variable Area: nvSRAM 64KB
Battery: Memory / Primary battery for clock data backup (Send back for replacement)
Touch Panel
Type
Resistive Film (analog)
Lifetime
1 million touches or more
Interface
Serial (COM1)
RS-232C/RS485 x 1
RS-232C (Connector type: RJ45, Isolation: None, Maximum baud rate: 115,200 bps, Cable Type: Shielded, Cable Maximum length: 15 m (49 ft), 5 Vdc power supply for RS-232C: None)
RS-485 (Connector type: RJ45, Isolation: None, Maximum baud rate: 115,200 bps, Cable Type: Shielded, Cable Maximum length: 200 m (656 ft), Polarization: Setting is required via software when connecting Multiple LTs. Refer to the "GP-Pro EX Device/ PLC Manual" for the setting. 5 Vdc power supply for RS-485: None) *4
CANopen (Master)
CAN-CiA (ISO 11898-2:2002 Part 2), Connector: D-sub9 (pin)
Ethernet
IEEE802.3 compliant Ethernet x 1
(Connector type: RJ45, Driver: 10 M half duplex (auto negotiation)/ 100 M full duplex (auto negotiation), Cable type: Shielded, Automatic cross-over detection: Yes)
USB (Type A)
USB 2.0 (Type A) x 1
(Power Supply Voltage: 5Vdc +/-5%, Maximum Current Supplied: 500mA, Maximum Transmission Distance: 5m (16.4 ft.))
USB (Mini-B)
USB 2.0 (Mini-B) x 1
Control
DIO (Source Type)
20 Points Standard Input (including 2 Points for Fast Input)
10 Points Standard Output, 2 Points for Fast Output
*2Use the screen area when the user font area's capacity is exceeded - for example, when an image font or a picture font is used.
*3Up to 60,000 steps can be converted in software. However, this reduces application memory capacity (for screen data) by 1 MB.
*42-wire connection is available for RS-485. When a Device/PLC supports 2-wire connection, 4 wires (RXD+, TXD+, RXD-, and TXD-) can be short-circuited to be 2 wires (RXD+ and TXD+ = D1, RXD- and TXD- = D0). For details on the connection, refer to the connection manual.
General Specifications
International Safety Standards
Rated Input Voltage
24 Vdc
Input Voltage Limits
20 to 28.8 Vd
Acceptable Voltage Drop
10 ms or less at 20.4 Vdc
Power Consumption
9 W or less
In-Rush Current
30 A or less at 28.8 Vdc
Voltage Endurance between power terminal and frame ground (FG)
500 Vdc for 1 minute
Insulation Resistance between power terminal and FG
10 MΩ or higher at 500 Vdc
Environmental Specifications
Standard compliance
IEC 61131-2
Ambient operating temperature for the display and the rear module
Horizontal installation
0 to 50°C (32 to 122°F)
Vertical installation
0 to 40°C (32 to 104°F)
Storage temperature
- 20 to 60°C (- 4 to 140°F)
Storage altitude
0 to 10,000 m (0 to 32,808 ft)
Operating altitude
0 to 2,000 m (0 to 6,560 ft)
Surrounding Air and Strage Humidity
5 to 85% w/o condensation (non-condensing, wet bulb temperature 39°C (102.2°F) or less)
Degree of pollution
IEC60664
2
Degree of protection
IEC61131-2
IP20 with protective covers in place
Corrosive gases
Free of corrosive gases
Dust
≤0.1 mg/m3 (10-7 oz/ft3) (non-conductive levels)
Atmospheric pressure (Operating Altitude)
800 to 1,114 hPa (2000 m (6,561 ft) or lower)
Vibration resistance
Mounted on a DIN rail
3.5 mm (0.138 in.) fixed amplitude from 5 to 8.4 Hz
9.8 m/s2 (1 gn) fixed acceleration from 8.4 to 150 Hz
Mounted on a panel
3.5 mm (0.138 in.) fixed amplitude from 5 to 8.6 Hz
9.8 m/s2 (1 gn) fixed acceleration from 8.6 to 150 Hz
Mechanical shock resistance
Mounted on a DIN rail
147 m/s2 (15 gn) for a duration of 11 ms
Mounted on a panel
147 m/s2 (15 gn) for a duration of 6 ms
Electrostatic discharge
IEC/EN 61000-4-2
8 kV (air discharge)
6 kV (contact discharge)
Rediated radio frequency electromagnetic fields
IEC/EN 61000-4-3
10 V/m (80 MHz to 3 GHz)
Fast transients / Burst noise
IEC/EN 61000-4-4
Power lines: 2 kV
Digital I/O: 1 kV
Relay outputs: 2 kV
Ethernet line: 1 kV
COM line: 1 kV
CAN line: 1 kV
Surge immunity
IEC/EN 61000-4-5
Power supply: CM: 1 kV; DM: 0.5 kV
Digital I/O: CM: 1 kV; DM: 0.5 kV
Shielded cable: 1 kV
CM = common drive
DM = differential drive
Conducted disturbances induced by radio-frequency fields
IEC/EN 61000-4-6
10 Veff (0.15 to 80 MHz)
Mains terminal dusturbance voltage
EN 55011 (IEC/CISPR11)
150 to 500 kHz, quasi peak 79 dBμV
500 kHz to 30 MHz, quasi peak 73 dBμV
Electric field strength
EN 55011 (IEC/CISPR11)
30 to 230 MHz, quasi peak 10 m @40 dBμV/m
230 MHz to 1 GHz, quasi peak 10 m @47 dBμV/m
Vibration immunity (operating)
IEC 61131-2
Protection structure
NEMA TYPE 4X (indoors, with panel embedded)
Protection (front module)
IP65f - (IEC 60529)
Protection (rear module)
IP 20 - (IEC 60529)
Shock immunity (operating)
IEC 61131-2
15 gn 11 ms
Cooling method
Natural air circulation
Weight
496 g (17.49 oz)
Color
Front module: PT404 Rear module: RAL 7032
Material
Front module: PC/PBT
Rear module: PC/PBT
Digital Inputs
Digital Input Characteristics
Rated Current
5 mA
Inrush Values
Voltage
30 Vdc
Current
6.29 mA max.
Input impedance
4.9 kΩ
Input type
Sink/Source
Rated voltage
24 Vdc
Maximum Allowable Voltage
28.8 Vdc
Input limit values
ON Voltage
15 Vdc or more (15 to 28.8 Vdc)
OFF Voltage
5 Vdc or less (0 to 5 Vdc)
ON Current
2.5 mA or more
OFF Current
1.0 mA or less
Isolation
Method
Photo coupler Isolation
Between internal logic
500 Vdc
Filtering
0.5 ms x N (N is 0 to 63)
IEC61131-2 edition 3 type
Type 1
Compatibility
Supports 2 wire and 3 wire sensors
Cable type and length
Shielded: Maximum 100 m (328 ft)
Non-shielded: 50 m (164 ft)
Terminal blocks
Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable
Input paralleling
No
* I0 and I1 are Fast input terminals and can be also used as a Standard input. For specifications, see the specifications of Fast Input.
High Speed Counter Input Characteristics
Rated Current
Voltage
24 Vdc
Current
7.83 mA
Inrush values
Voltage
30 Vdc
Current
9.99 mA
Input impedance
3.2 kΩ
Input type
Sink/Source
Rated voltage
24 Vdc
Maximum Allowable Voltage
28.8 Vdc
Input limit values
ON Voltage
15 Vdc or more
OFF Voltage
5 Vdc or less
ON Current
5 mA or more
OFF Current
1.5 mA or less
Isolation
Method
Photo coupler Isolation
Between channels logic
500 Vdc
Filtering
None, 4 μs, 40 μs
IEC61131-2 edition 3 type
Type 1
Compatibility
Supports 2 wire and 3 wire sensors
Cable
Type
Shielded
Length
Maximum 10 m (33 ft)
Terminal blocks
Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable
Maximum frequency
· 100 kHz is the maximum frequency for Single-phase
· 50 kHz is the maximum frequency for 2-phase
· Duty Rate: 45 to 55%
(1) When connecting as power surges * To use 3.0A common current, connect to A3 and A4 for V1+. (B3 and B4 for V1-)
Caution: Q0 and Q1 circuits are push-pull circuits. The following is the operation of the push-pull circuit at the Sink Output and the Source Output.
Sink Output: +24(V) is output to terminal Q0, Q1 when the logic for Q0, Q1 is off
Source Output: 0(V) is output to terminal Q0, Q1 when the logic for Q0, Q1 is off
Standard Output terminals Q2 or later are common open collector outputs.
Do not connect Fast Output terminals Q0, Q1 and Standard Output terminals Q2 or later. It will short.
If you add a manual circuit to terminal Q0, Q1, isolate the manual circuit and terminal Q0, Q1 with a relay. Without isolation, it will short.
Between power supply port and protective earth ground (PE) = 500 Vdc
10 MΩ or more
Residual voltage
for I = 0, 1 A
1.5 Vdc or less
Delay
Off to on (50 mA load): 1.1ms
On to off (50 mA load): 1.1ms
NOTE: The delay is not including the cable delay.
Minimum load impedance
80 Ω
Maximum Pulse output frequency
50 KHz
Maximum PWM output frequency
65 kHz
Accuracy Pulse Output/ PWM Output
Frequency
Accuracy
Duty
10 to 100 Hz
0.1%
0 to 100%
10 to 1000 Hz
1%
1 to 99%
1.001 to 20 kHz
5%
5 to 95%
20.001 to 45 kHz
10%
10 to 90%
45.001 to 65 kHz
15%
15 to 85%
Duty rate range
1 to 99%
Cable
Type
Shielded, including 24 Vdc power supply
Length
Maximum 5 m (16 ft)
Terminal blocks
Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable
NOTE: When using the acceleration/deceleration pulse output, there is a 1% maximum error for the frequency.
Caution: Q0 and Q1 circuits are push-pull circuits. The following is the operation of the push-pull circuit at the Sink Output and the Source Output.
Sink Output: +24(V) is output to terminal Q0, Q1 when the logic for Q0, Q1 is off
Source Output: 0(V) is output to terminal Q0, Q1 when the logic for Q0, Q1 is off
Standard Output terminals Q2 or later are common open collector outputs.
Do not connect Fast Output terminals Q0, Q1 and Standard Output terminals Q2 or later. It will short.
If you add a manual circuit to terminal Q0, Q1, isolate the manual circuit and terminal Q0, Q1 with a relay. Without isolation, it will short.
Terminal Blocks
Pin Arrangement
Group
Pin
Signal Name
Group
Pin
Signal Name
Fast Output
A1
V0+
Fast Output
B1
V0-
A2
Q1
B2
Q0
Standard Output
A3
V1+
Standard Output
B3
V1-
A4
V1+
B4
V1-
A5
Q3
B5
Q2
A6
Q5
B6
Q4
Pin Arrangement
Group
Pin
Signal Name
Group
Pin
Signal Name
Standard Output
C1
Q7
Standard Output
D1
Q6
C2
Q9
D2
Q8
C3
Q11
D3
Q10
Fast Input/Standard Input
C4
I0
Fast Input/Standard Input
D4
IC0
C5
I1
Standard Input
D5
I2
Standard Input
C6
I3
D6
IC1
C7
I5
D7
I4
C8
I7
D8
I6
C9
I9
D9
I8
C10
IC2
D10
IC2
C11
I11
D11
I10
C12
I13
D12
I12
C13
I15
D13
I14
C14
I17
D14
I16
C15
I19
D15
I18
External Dimensions
Panel Cut-out
* Without the tee option, the display module supports a rotating torque of 2.5 N•m (22.12 lbin).
Product & Technology News
PS6000 makes the next stage of your digital transformation