Specification of AGP3650-U1-D24

GP-3650U 
Model: AGP3650-U1-D24

Thumbnail
  • Serial x2
  • Ethernet
  • Video In
  • Video Unit
  • Fieldbus
  • I/O
  • USB
  • CF Card
M Class (Multi-media) /   TFT Color LCD (Ultra High-brightness)   (65,536 colors) /   SVGA

Functional Specification

Display Type TFT Color LCD (Ultra luminance)
Display Size 12.1"
Resolution 800 X 600 pixels (SVGA)
Dot pitch W0.3075 X H0.3075mm [W0.01 X H0.01in.]
Effective Display Area W248 X H186.5mm [W9.76 X H7.34in.]
Display Colors 65,536 Colors (No blink)/16,384 Colors (Blink)
Backlight CCFL (User nonreplaceable parts. Factory replacement required.)
Brightness Control 8 Levels (Adjusted with the touch panel)
Contrast Control Not applicable
Backlight Service Life 40,000 hrs. or more (continuous operation at 25 ℃ before backlight brightness decreases to 50 %)
Language Fonts Japanese: 6,962 (JIS Standards 1 & 2) (including 607 non-kanji characters), ANK: 158 (Korean fonts, Simplified Chinese and Traditional Chinese fonts are downloadable.
Character Sizes Standard font: 8 x 8, 8 x 16, 16 x 16 and 32 x 32 pixel fonts, Stroke font: 6 to 127 pixel fonts, Image font: 8 to 72 pixel fonts
Font Sizes Standard font: Width can be expanded up to 8 times., Height can be expanded up to 8 times.*1
Text 8 x 8 dots 100 char. X 75 rows
8 x 16 dots 100 char. X 37 rows
16 x 16 dots 50 char. X 37 rows
32 x 32 dots 25 char. X 18 rows
Control Memory Variable Area SRAM 64 KB (uses lithium battery)*2
Program Area 132KB FLASH EPROM*3
Number of Step Equivalent to 15,000 steps*3
Application Memory FLASH EPROM 10 MB*4
Data Backup SRAM 320KB (uses lithium battery)*2
Clock Accuracy ±65 sec/month (deviation at room temperature and power is OFF)*5
Touch Panel Type Resistive Film (analog)
Touch Panel Resolution 1,024 X 1,024
Touch Panel Service Life 1,000,000 times or more
Interface Serial (COM1) RS-232C/422/485, Asynchronous Transmission, Data Length: 7 or 8 bit, Parity: none, Even or Odd, Stop Bit: 1 or 2 bit, Data Transmission Speed: 2,400 bps to 115.2 kbps, Connector: D-Sub9 (plug)
Serial (COM2) RS-422/485, Asynchronous Transmission, Data Length: 7 or 8 bit, Parity: none, Even or Odd, Stop Bit: 1 or 2 bit, Data Transmission Speed: 2,400 bps to 115.2 kbps, 187.5kbps (MPI), Connector: D-Sub9 (socket)
Ethernet (LAN) IEEE802.3i/IEEE802.3u, 10BASE-T/100BASE-TX, Connector: Modular jack (RJ-45)×1
Expansion Unit 1 Communication Expansion Unit x 1
Expansion Unit 2 VM/DVI Input Expansion Unit X 1
USB (TYPE-A) Conforms to USB1.1.(TYPE-A conn.) X 2, Power Supply Voltage: DC5V±5%, Output Current: 500mA (max.), Communication Distance: 5m (max.)
Expansion Memory Function Expansion Memory X 1
CF Card Compact Flash CF Card Slot (TYPE-II) X 1
Video Input NTSC: 59.9Hz, PAL: 50Hz, SECAM: 50Hz, Connector: RCA 75Ω X 1
Sound Input MIC or LINE input (software switch), Connector: MINI-JACK Φ3.5 X 1
Sound Output Speaker Output, 70mW (Rated Load: 8Ω, Frequency: 1kHz), Connector: 2-piece terminal block (AUX) X 1
AUX Input/Output Alarm Output, RUN Output, Buzzer Output, Rated Voltage: DC24V, Rated Current: 50mA, Remote Reset Input, Input Voltage: DC24V, Connector: 2-piece terminal block (AUX) X 1
  1. *1     Other font sizes can be set up with the Editor software.
  2. *2     A Lithium battery's lifetime is:
    10 years when the battery's ambient temperature is 40 oC or less.
    4.1 years when the battery's ambient temperature is 50 oC or less.
    1.5 years when the battery's ambient temperature is 60 oC or less.
    When used for back up: Approximately 100 days, with a fully charged battery.
    Approximately 6 days, with a half-charged battery.
  3. *3     Available only in units supporting logic programs
  4. *4     Capacity available for user application. 8 MB available if GP-Pro EX Ver. 2.5 or earlier is used.
  5. *5     Depending on the operating temperature and age of unit, the clock can deviate from -380 to +90 sec/month. For systems where this level of deviation is a problem, the user should monitor and make adjustments when required.

General Specification

International Safety Standards
Rated Input Voltage DC 24 V
Input Voltage Limits DC 19.2 to 28.8 V
Allowable Voltage Drop 10 ms or less
In-Rush Current 30 A or less
Voltage Endurance AC 1,000 V, 20 mA for 1 min (between charging and FG terminals)
Insulation Resistance DC500V 10MΩ (min.), (between charging and FG terminals)
Surrounding Air Temperature 0 to 50℃*6
Storage Temperature -20 to +60℃
Ambient Humidity 10 to 90% RH (Wet bulb temperature: 39℃ max. - no condensation.)
Storage Humidity 10 to 90% RH (Wet bulb temperature: 39℃ max. - no condensation.)
Dust 0.1mg/m³ and below (non-conductive levels)
Pollution Degree For use in Pollution Degree 2 environment
Atmosphere Free of corrosive gases
Air Pressure (altitude range) 800 to 1,114hPa (2,000 meters max.)
Vibration Resistance IEC/EN61131-2 compliant, 5 to 9Hz Single amplitude 3.5mm [0.14in.], 9 to 150Hz Fixed acceleration: 9.8m/s², X,Y,Z directions for 10 cycles (100 minutes)
Concussion Resistance IEC/EN61131-2 compliant, 147m/s² X,Y,Z directions for 3 times
Noise Immunity Noise Voltage: 1,000 Vp-p, Pulse Duration: 1 µs, Rise Time: 1 ns, (via noise simulator)
Electrostatic Discharge Immunity Contact Discarge Method: 6kV (IEC/EN61000-4-2 Level 3)
Grounding Functional grounding: Grounding resistance of 100Ω, 2mm² or thicker wire, or your country's applicable standard. (Same for FG and SG terminals)
Structure IP65f (on the front panel when properly installed in an enclosure)*7
Installation Configuration Embedded panel
Cooling Method Natural air circulation
Weight Approx. 3.0kg [6.6lb] max. (unit only)
External Dimensions W313 X H239 X D56mm, [W12.32 X H9.41 X D2.20in.]
Panel Cut Dimensions W301.5 x H227.5 mm [W11.87 x H8.96 in.], Panel thickness area: 1.6 to 10 mm [0.06 to 0.39 in.]*8
  1. *6     When using monochrome/STN Color LCD model in an environment where the temperature becomes or exceeds 40℃ for an extended period of time, the screen contrast level may decrease from its original level of brightness.
  2. *7     The front face of the GP unit, installed in a solid panel, has been tested using conditions equivalent to the standards shown in the specification. Even though the GP unit's level of resistance is equivalent to these standards, oils that should have no effect on the GP can possibly harm the unit. This can occur in areas where either vaporized oils are present, or where low viscosity cutting oils are allowed to adhere to the unit for long periods of time. If the GP's front face protection sheet becomes peeled off, these conditions can lead to the ingress of oil into the GP and separate protection measures are suggested., Also, if non-approved oils are present, it may cause deformation or corrosion of the front panel's plastic cover. Therefore, prior to installing the GP be sure to confirm the type of conditions that will be present in the GP's operating environment., If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from the panel, the original level of the protection cannot be guaranteed. To maintain the original protection level, be sure to replace the installation gasket regularly.
  3. *8     Regarding dimensional tolerance, everything +1/-0 mm [+0.04/-0 in.] and R in angle are below R3 [R0.12 in.].

External Dimensions / Interfaces / Panel Cut-out / Cable Attached Dimensions