Specification of FP3710-T42-24V-U 

 

Model (Global Code): FP3710-T42-24V-U (PFXFP3710T2DU)
 

Functional Specification

Display Type TFT Color LCD
Display Size 15"
Resolution 1,024 x 768 pixels (XGA)
Dot pitch W0.297 x H0.297 mm [W0.01 x H0.01 in.]
Effective Display Area W304.1 x H228.1 mm [W11.97 x H8.98 in.]
Display Colors 16,777,216 Colors
Backlight LED backlight (The backlight cannot be replaced by the user. The unit must be sent back for backlight replacement.)
Brightness Control Available*1
Contrast Control Available
Backlight Service Life 50,000 hrs. or more (continuous operation at 25 °C before backlight brightness decreases to 50% or backlight starts to blink)
Touch Panel Type Resistive Film (analog)
Touch Panel Resolution 1,024 x 1,024
Touch Panel Service Life 1,000,000 times or more
Touch Panel Interface RS-232C or USB (USB2.0, TYPE-B)
Interface USB (TYPE-A) Conforms to USB2.0 (TYPE-A) x 1, Power Supply Voltage: DC 5 V ±5 %, Output Current: 500 mA or less, Communication Distance: 5 m or less
Video Analog RGB input connector: mini D-Sub15 (socket) x 1,
DVI-D input, Connector: DVI-D 24 pin (socket) x 1*2
  1. *1     Specified on OSD setting.
  2. *2     FPs which have a mark in hardware revision "2" support DVI Hot Plug Detect function.

General Specification

International Safety Standards
  • UL
  •  
  • cUL
  •  
  • CE
  •  
  • Gost-R
Rated Input Voltage DC24 V
Input Voltage Limits DC19.8 to 28.8 V
Allowable Voltage Drop 5ms or less
Power Consumption 40W or less
In-Rush Current 30A or less
Voltage Endurance AC1000V 20mA for 1 minute (between charging and FG terminals)
Insulation Resistance DC500V 10MΩ or more (between charging and FG terminals)
Surrounding Air Temperature 0 to 50 °C
Storage Temperature -20 to +60 °C
Ambient Humidity 10 to 90 % RH (Wet bulb temperature: 39 °C or less - no condensation.)
Storage Humidity 10 to 90 % RH (Wet bulb temperature: 39 °C or less - no condensation.)
Dust 0.1 mg/m³ or less (non-conductive levels)
Pollution Degree For use in Pollution Degree 2 environment
Atmosphere Free of corrosive gases
Air Pressure (altitude range) 800 to 1,114 hPa (2,000 m above sea level or less)
Vibration Resistance IEC/EN61131-2 compliant, 5 to 9 Hz Single amplitude 3.5 mm [0.14 in.], 9 to 150 Hz Fixed acceleration: 9.8 m/s², X, Y, Z directions for 10 cycles (100 min)
Concussion Resistance IEC/EN61131-2 compliant, 147 m/s², X, Y, Z directions for 3 times
Noise Immunity Noise Voltage: 1,000Vp-p, Pulse Duration: 1μs, Rise Time: 1ns
Electrostatic Discharge Immunity Contact Discharge Method: 6 kV (IEC/EN61000-4-2 Level 3)
Grounding Protective grounding: Grounding resistance of 100 Ω, 2 mm² or thicker wire, or your country's applicable standard. (Same for FG and SG terminals)
Structure Equivalent to IP65f (on the front panel when properly installed in an enclosure)*3
Installation Configuration Embedded panel
Cooling Method Natural air circulation
Weight Approx. 7 kg [15.4 lb] or less (display unit only)
External Dimensions W395 x H294 x D60 mm [W15.55 x H11.57 x D2.36 in.]
Panel Cut Dimensions W383.5 x H282.5 mm [W15.1 x H11.12 in.], Panel thickness area: 1.6 to 10 mm [0.06 to 0.39 in.]*4
  1. *3     The front face of the FP unit, installed in a solid panel, has been tested using conditions equivalent to the standards shown in the specification. Even though the FP unit's level of resistance is equivalent to these standards, oils that should have no effect on the FP can possibly harm the unit. This can occur in areas where either vaporized oils are present, or where low viscosity cutting oils are allowed to adhere to the unit for long periods of time. If the FP's front face protection sheet becomes peeled off, these conditions can lead to the ingress of oil into the FP and separate protection measures are suggested., Also, if non-approved oils are present, it may cause deformation or corrosion of the front panel's plastic cover. Therefore, prior to installing the FP be sure to confirm the type of conditions that will be present in the FP's operating environment., If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from the panel, the original level of the protection cannot be guaranteed. To maintain the original protection level, be sure to replace the installation gasket regularly.
  2. *4     Regarding dimensional tolerance, everything +1/-0 mm [+0.04/-0 in.] and R in angle are below R3 [R0.12 in.].