• Info
  • Specifications
 

OD Range Analogue Signal Conditioner - Specification

Analogue Signal Conditioner
Power Requirements OD2 OD4 OD5
Voltage Range 13 VDC to 42 VDC 10 VDC to 30 VDC 90 VAC to 264 VAC
Current Range (mA) Up tp 30 140 @ 10 V to
50 @ 30 V
250 @ 120 V to
100 at 250
Frequency Range (Hz) - 47 to 63
 
Sensor Excitation
Primary Voltage (Vrms) 0 - 9 3
Primary Frequency (kHz) 5 or 13 nominal 2.5 or 5 nominal
10 or 13 nominal (Half Bridge variant)
 
Signal Input (Sensor Sensitivity Range)
Input Range 30 to 530 mV/V1 55 mV to 5000 mV (LVDT Full Range)
Input Load Resistance (kΩ) 100 2, 10, 100
Options - Forward and Reverse polarity, Half Bridge
1For sensors with a sensitivity greater than 530 mV/V, an adjustable attenuator is required.
Signal Output
Voltage Output (VDC) - Up to ± 10
Current Output (mA) 4 - 20 (2 wire)
0 - 20 (4 wire)
Up to ± 20 mA into 150 Ω load
Output Ripple 38 µA rms < 1 mVrms
Output Offset Up to 100% Maximum Gain (Coarse and Fine adjustment)
Temperature Coefficient Gain < 0.01% FRO/°C
Temperature Coefficient Offset < 0.01% FRO/°C
Warm Up Time 15 Minutes (recommended)
Linearity 0.02% FRO 0.1% FRO
Bandwidth-3db (Hz) 25 500 typical
 
Environmental
Operating Temperature Range 0 to +60 °C (+32 to +140 °F)
Storage Temperature Range -40 to +80 °C
(-42 to +176 °F)
-20 to +85 °C
(-4 to +185 °F)
IP Rating IP 65 IP 40
 
Mechanical and Connections
Sensor Internal Terminal Block 5 pin Circular DIN
Power Supply Internal Terminal Block IEC320 C14
Output Signal Internal Terminal Block
Enclosure Dimensions without Connectors (mm) 120 x 80 x 54.5 120 x 60 x 40
Weight (g) 220 300
Material Light Grey ABS Die-Cast Zinc Alloy (painted)
 
 

 

Product and Technology News

Orbit® Gauge Software

Application Selector

Solartron Metrology

Download Catalogue